High pressure means real hazards#
A charged pneumatic system stores energy that can release violently if a fitting fails or tubing whips free. The FRC Pneumatics Manual describes a circuit with two sides: a high-pressure (storage) side at up to 120 psi and a working-pressure side at up to 60 psi. Knowing where each pressure lives — and how to bleed it to zero — is the core of pneumatics safety.
Required components on the high-pressure side#
The manual lists the components a legal FRC high-pressure side must include:
- Compressor — compresses air into the system.
- Pressure Relief Valve — relieves excess pressure if the system exceeds its set point. It is set to 125 psi and must be connected to the compressor's output port via hard fittings so it can always protect the compressor.
- Air Storage Tank(s) — store compressed air for use during a match.
- Pressure Switch — tells the controller whether to turn the compressor on or off (it cuts the compressor at ~120 psi).
- Pressure Gauges — the system must have a minimum of two gauges, indicating the stored and working pressures.
- Vent Plug (manual vent valve) — releases all stored pressure when operated by hand. This is your safety "off switch."
- Pressure Regulator — the "primary" regulator reduces pressure from the permitted storage pressure (120 psi) down to the permitted working pressure (60 psi). Only additional pressure sensors (transducers) or filters are allowed elsewhere on the high-pressure side.
Force scales with cylinder bore: a 2-inch bore cylinder at 60 psi can apply roughly 188 pounds of force — respect that energy when a mechanism actuates.
The controller#
A pneumatics controller runs the compressor and actuates the solenoid valves. Two are legal: the REV Robotics Pneumatic Hub (PH), which controls up to 16 solenoid channels (16 single-acting or 8 double-acting solenoids), and the CTR Electronics Pneumatics Control Module (PCM), which controls up to 8 solenoid channels (8 single-acting or 4 double-acting) and uses a digital pressure switch. All solenoids on a robot must be the same voltage (either 12V or 24V).
Safe assembly#
- Seal threaded (NPT) connections with PTFE thread-sealing tape (a single wrap, applied so it tightens with the threads) and snug them with wrenches.
- Cut tubing square and leave it long enough to avoid strain on the joint. To release tubing from a push-to-connect fitting, press and hold the colored collar inward, then pull the tube out.
- Validate the relief valve and run a leak test as described in the manual before relying on the system.
Safe servicing — the golden rule#
Before working on any part of the pneumatic system, follow the stored-energy procedure: open the manual vent valve to vent all compressed air to the atmosphere, and verify that every pressure gauge reads zero. Never loosen a fitting, swap a cylinder, or reach into a mechanism's path while the system holds pressure. When the robot is enabled to deploy code, charge pneumatics, or test functions, keep clear space so any mechanism can move unexpectedly to its full extent.
the part worth keeping
Key takeaways
- FRC pneumatics has a 120 psi storage side and a 60 psi working side, set by the primary regulator.
- Required parts include a 125 psi relief valve mounted to the compressor via hard fittings, storage tank(s), a pressure switch, two gauges, a manual vent plug, and the primary regulator.
- Legal controllers are the REV Pneumatic Hub (16 channels) and the CTRE PCM (8 channels); all solenoids share one voltage (12V or 24V).
- Always vent the system until every gauge reads zero before servicing, and keep clear of mechanisms that can move to full extent.
SafetyBattery, Pneumatics, and Electrical Safetylesson 3 of 4
Keep going
Take the quiz+10 XP with an accountMore in Battery, Pneumatics, and Electrical Safety
where this came from
Sources and corrections
This lesson is AI-assisted: drafted from primary sources, then reviewed and edited by hand. Errors still get through. When one is reported we fix it and write down what changed, in public, in the corrections log.
sources and further reading
- firstinspires.orgFRC Pneumatics Manual (Rev. Jan 2023)
- docs.wpilib.orgWPILib Docs — Generating and Storing Pressure
clipped to this lesson
Articles that go further on this
The lesson gets you through the topic. These go wider on it, and they read in one sitting.
- 9 min readFRC Pneumatics: How to Design, Wire, and Program a Pneumatic SystemComplete FRC pneumatics guide: components, the REV Pneumatic Hub vs PCM, single vs double solenoids, safe wiring, WPILib programming, and the 60/120 psi limits./blogread it
- 7 min readFRC Shop Safety and PPE: Eye Protection Rules, Machine Rules, and Real InspectionsFRC shop safety: when eye protection is required, machine-specific rules, the pit safety kit, and how to run a real safety inspection./blogread it
answer sheet
Lesson quiz
All 4 right completes the lesson. Miss one and only that question comes back, anything you already answered correctly stays banked.
0 of 4 answered
01In an FRC pneumatic system, what are the maximum stored (main) pressure and maximum working pressure?
02What is the purpose of the relief valve required on an FRC compressor's output, and what pressure is it set to?
03Before working on a robot's pneumatic system, what must you do first?
04Which pneumatics controllers are legal in FRC, and how many solenoid channels does each support?
Answer every question to submit.
All 28 lessons in Safetyopenclose
01 / culture-and-roles
02 / ppe-and-shop-safety
03 / battery-pneumatics-electrical
04 / events-and-program
05 / safety-worked-examples-mini-projects
- Not read yet:Mini-Project: A Battery Management & Logging System
- Not read yet:Mini-Project: Write a Robot Lockout/Tagout (LOTO) Procedure
- Not read yet:Worked Example: Current Limits That Prevent Brownouts
- Not read yet:Mini-Project: Assemble a Competition Pit Safety Kit
- Not read yet:Mini-Project: Run a Mock Pit Safety Inspection
06 / safety-common-mistakes-troubleshooting
- Not read yet:Troubleshooting Brownouts and Power Sag
- Not read yet:Battery Handling Mistakes That Cause Injuries and Fires
- Not read yet:Electrical Isolation and Wiring Mistakes Inspectors Fail You For
- Not read yet:Stored-Energy Surprises: Pneumatics and Springs
- Not read yet:Pit and Shop Conduct Mistakes That Hurt Your Judging
07 / safety-advanced-engineering-case-studies